Yaskawa VS-616G5 Series Revision F Programming Manual User Manual

Page 140

Advertising
background image

140

VS-616G5 Programming Manual

G

ro

up

E

M

ot

or

Fu

nc

tio

n

E3

C

on

tro

l M

et

ho

d

E3-01

Motor 2 Control
Method Selection
(Control Method)

0~3

1

2

0: (V/F Control)
1: (V/F w/PG Fdbk)
2: (Open Loop Vector)
3: (Flux Vector)

x

A

A

A

A

Fu

nc

tio

n

E4

V

/F

P

at

te

rn

2

E4-01

Motor 2 Max. Out-
put Frequency
(Max Frequency)

40.0~
400.0

0.1Hz

60.0

x

A

(Note

14)

A

(Note

14)

A

(Note

14)

A

(Note

14)

E4-02

Motor 2 Max.
Voltage
( Max Voltage)

0.0~

255.0
(Note

13)

0.1V

200.0
(Note

13)

x

A

(Note

14)

A

(Note

14)

A

(Note

14)

A

(Note

14)

E4-03

Motor 2 Max.
Voltage Frequency
(Base Frequency)

0.0~

400.0

0.1Hz

60.0

x

A

(Note

14)

A

(Note

14)

A

(Note

14)

A

(Note

14)

E4-04

Motor 2 Mid.
Output Frequency 1
(Mid Frequency)

0.00~
400.0

0.1Hz

3.0*

* Factory setting differs
depending on the control
method [E3-01]

x

A

(Note

14)

A

(Note

14)

A

(Note

14)

F

(Note

14)

E4-05

Motor 2 Mid.
Output Frequency
Voltage 1
(Mid Voltage)

0.0~

255.0
(Note

13)

0.1V

11.0

(Note

13)*

* Factory setting differs
depending on the control
method [E3-01]

x

A

(Note

14)

A

(Note

14)

A

(Note

14)

F

(Note

14)

E4-06

Motor 2 Min.
Output Frequency
( Min Frequency)

0.0~

400.0

0.1Hz

0.5*

* Factory setting differs
depending on the control
method [E3-01]

x

A

(Note

14)

A

(Note

14)

A

(Note

14)

A

(Note

14)

E4-07

Motor 2 Min.
Output Frequency
Voltage
(Min Voltage)

0.0~

255.0
(Note

13)

0.1V

2.0*

(Note13)

* Factory setting differs
depending on the control
method [E3-01]

x

A

(Note

14)

A

(Note

14)

A

(Note

14)

F

(Note

14)

Note 13: This value is for the 200V class. For 400V class, the value is twice that of 200V class. For 575V class, then modify the values by 575/200
Note 14: Control mode is determined by E3-01.

Function

Parameter

No.

Name

(Digital Operator

Display)

Setting

Range

Setting

Unit

Factory

Setting

Remarks

(Digital Operator Display)

Change

during

Operation

o: Enabled

x: Disabled

Parameter Access Level

User

Setting

V/f

V/f

w/

PG

Open

Loop

Vector

Flux

Vector

Appendix

VS-616G5 Parameter List E Motor

Advertising