Yaskawa VS-616G5 Series Revision F Programming Manual User Manual

Page 84

Advertising
background image

V/f

V/f w/PG Open Loop

Vector

Flux

Vector

84

VS-616G5 Programming Manual

Section H: Control Circuit Terminals

H1 Digital Inputs

· Terminal 13/14 Selection (setting: “1F”)

Open:

Terminal 13 is used for the master frequency reference.

Closed:

Terminal 14 is used for the master frequency reference.

Note:

When the set value of Terminal 14 Selection (H3-09) is other than “1F” and the contact input
is set for terminal 13/14 selection (H1-__ = “1F”), a setting error (OPE3) occurs.

· External Fault (setting: “20-2F”)

Use this contact input to select how the inverter responds to an external fault.

Notes:

1. N.O. = normally open contact; N.C. = normally closed contact
2. Setting “24” is the factory default.
3. Set up the external fault function according to the following tree:

External Fault Selection

Setting

Result

Input Level Selection

Detection Method

External Fault Action

N.O.

N.C.

Always During Run Ramp to Stop Coast to Stop

Fast-stop

Alarm Only

20

24

28

2C

22

26

2A

2E

21

25

29

2D

23

27

2B

2F

Advertising