VS-616G5 Programming Manual

63

V/f

V/f w/PG Open Loop

Vector

Flux

Vector

Sets the motor phase-to-phase resistance value in units of 0.01W.

The default setting varies depending on the inverter model setting (O2-04).

Sets the motor leakage inductance in units of 0.1%. The default setting varies depending on the
inverter model setting (O2-04).

F

Option Parameters

F1

PG Option Set-up
These parameters can be accessed during operation using a pulse generator (PG) for speed feedback.

When access level is BASIC (A1-03), the parameter is not displayed unless the option card is con-
nected.

Setting Range:

0 to 60000

Factory Default:

1024

Sets the number of PG pulses per motor revolution (pulses/rev).

Selects the stopping method when a disconnected PG is detected.

E5-05 Motor 2 Terminal Resistance

Term Resistance

A

A

A

A

E5-06 Motor 2 Leakage Inductance

Leak Inductance

A

A

A

F1-01 PG Pulses per Revolution

PG Pulses/Rev

Q

Q

F1-02 PG Disconnection Detection Stopping Method

PG Fdbk Loss Sel

B

B

Setting

Description

0

Ramp to stop - according to C1-02

1

Coast to stop (factory default)

2

Fast-stop according to C1-09

3

Alarm flashes, operation continues (this setting is disabled
during flux vector control)

Phase-to-Phase Resistance at

273 + (25ºC + insulation class temperature) / 2

273 + insulation class temperature

Motor Terminal Resistance = Insulation Class Temperature ×

Section F: Option Parameters

F1 PG Option Set-up