Section H: Control Circuit Terminals

H1 Digital Inputs

·Speed Search 1 and Speed Search 2 (Set value = 61 and 62)

· Energy Save Mode (Set value = 63)
After the energy savings input is closed and the output frequency is equal to or greater than (b8-02)
energy savings start frequency, the output voltage drops to the value in (b8-01) energy savings gain.
The output voltage increases and decreases based on L2-04 (voltage recovery time).

a = (L2-03) minimum
baseblock time
b = (L2-04) voltage
recovery time c
= speed search decel
time
d = V/f pattern reduction
during speed search

Output

Current

Output

Voltage

Motor

RPM

Output

Frequency

Run

Command

Inverter is in

speed search

mode

Inverter is in

run mode

b

c

d

Searches from max
frequency when using
61, and set frequency
when using 62.

a

n

n

Set values 61 and 62

are only available in the
open loop V/f and open
loop flux vector control
modes.

b3-02
(150% )

Energy

saving

command

Output

Frequency

Run

Command

t

t

t

b8-02

t

Output

Voltage

b8-01