V/f

V/f w/PG Open Loop

Vector

Flux

Vector

· PID Integral reset (Set value = 30)

Open: PID Integral values are added.
Closed: PID Integral value is set to zero.

· PID Control Integral Hold (Set value = 31)

<1110>

Closed: Integral value of the PID control is held.

· DC Injection Braking Command (setting: “60”)

When a DC injection braking command is input while the inverter is stopped, DC injection braking
operation is activated. When a run command or a jog command is input, DC injection braking is
released to start operation (operation has priority).

H1-__ = “24”

Depress the Data/Enter key.

Input Level Selection

Detection Method

External Fault Action

N.O. Contact
N.C. Contact

Always

During Run

Ramp to Stop
Coast to Stop
Fast-stop

Depress

Alarm Only

the

∧

key.

DC Injection Braking Command

Fwd Run Command

ON

OFF

OFF

Output Frequency

ON

OFF

OFF

DC Injection

Braking

DC Injection

Braking

DC Injection Braking

Start Frequency

(B2-01)

Figure 35 DC Injection Braking Contact Input Timing Diagram

Section H: Control Circuit Terminals

H1 Digital Inputs