Yaskawa VS-616G5 Series Revision F Programming Manual User Manual
Page 148

148
VS-616G5 Programming Manual
Te
rm
in
al
An
al
og
In
pu
ts
H3-06
(Terminal 16 Gain)
0.0~
1000.0
0.1%
100.0
—
o
B
B
B
B
H3-07
(Terminal 16 Bias)
–100.0
~ +100.0
0.1%
0.0
—
o
B
B
B
B
H3-08
Signal Level
Selection Terminal
14
(Term 14 Signal)
0, 1, 2
1
2
0: (0 - 10 VDC)
1: (–10 +10 VDC)
2: (4 - 20 mA)
x
A
A
A
A
H3-09
Multi-function
Analog Input
Terminal 14
(Terminal 14 Sel)
1~1F
1
1F
The function choices for terminal
14 are the same as the choices
for terminal 16 [ see H3-05},
except that [setting 0] “Auxiliary
Reference” is not available.
x
A
A
A
A
H3-10
Terminal 14 Gain
(Terminal 14 Gain)
0.0~
1000.0
0.1%
100.0
—
o
A
A
A
A
H3-11
Terminal 14 Bias
(Terminal 14 Bias)
–100.0
~
+100.0
0.1%
0.0
—
o
A
A
A
A
H3-12
Analog Input Filter
Time Constant
(Filter Avg Time)
0.00~
2.00
0.01s
0.00
—
x
A
A
A
A
Function
Parameter
No.
Name
(Digital Operator
Display)
Setting
Range
Setting
Unit
Factory
Setting
Remarks
(Digital Operator Display)
Change
during
Operation
o: Enabled
x: Disabled
Parameter Access Level
User
Setting
V/f
V/f
w/
PG
Open
Loop
Vector
Flux
Vector
Appendix
VS-616G5 Parameter List H Terminals