VS-616G5 Programming Manual

71

V/f

V/f w/PG Open Loop

Vector

Flux

Vector

F5

DO-02 Set-up

The DO-02C option card has 2 form C type dry contacts. Each of the dry contacts can be individually
set by F5-01 and F5-02.
The DO-02C option card connects to the control board at 3CN.
The table is a list of items that can be selected.

Selects the multi-function output selections for channel 1 of the DO-02C option.
For detailed information on these settings, refer to section H2, Digital Outputs, on page 88.

Setting Range:

Same as F5-01

Factory Default:

Zero speed (setting = “1”)

Selects the multi-function output selections for channel 2 of the DO-02C option.

F5-01 DO-02C Digital Output Channel 1 Selection

DO-02 CH1 Select

A

A

A

A

Setting

Description

Setting

Description

0

During run 1 (factory default)

13

Fref/Fout agree 2

1

Zero speed

14

Fref/set agree 2

2

Fref/Fout agree 1

15

Frequency detection 3

3

Fref/set agree 1

16

Frequency detection 4

4

Frequency detection 1

17

Torque detection 1 (N.C.)

5

Frequency detection 2

18

Torque detection 2 (N.O.)

6

Inverter ready

19

Torque detection 2 (N.C.)

7

DC bus undervoltage

1A

Reverse direction

8

Baseblock 1

1B

Baseblock 2

9

Option frequency reference

1C

Motor 2 selected

A

Remote operation

1D

Regenerating

B

Torque detection 1 (N.O.)

1E

Restart enabled

C

Loss of reference

1F

Overload (OL1)

D

DB overheat

20

OH pre-alarm

E

Fault

30

Current/torque limit

F

Not used

31

Speed limit

10

Minor fault

33

Zero servo end

11

Reset command active

37

During run 2

12

Timer output

-

--

F5-02 DO-02C Digital Output Channel 2 Selection

DO-02 CH2 Select

A

A

A

A

Section F: Option Parameters

F5 DO-02 Option Set-up