Yaskawa VS-616G5 Series Revision F Programming Manual User Manual
Page 142

142
VS-616G5 Programming Manual
G
ro
up
F
O
pt
io
ns
*
Fu
nc
tio
n
F1
P
G
O
pt
io
n
Se
tu
p
F1-09
Overspeed
Detection Delay
Time
(PG Overspd Time)
0.0~2.0
0.1s
0.0*
* When A1-02=1 [V/f w/PG] fac-
tory setting is 1.0. When A1-
02=3 [ Flux Vector] factory set-
ting is 0.0.
x
-
A
-
A
F1-10
Excessive Speed
Deviation Detection
Level
(PG Deviate Level)
0~50
1%
10
—
x
-
A
-
A
F1-11
Excessive Speed
Deviation detection
Delay Time
(PG Deviate Time)
0.0~
10.0
0.1s
0.5
—
x
-
A
-
A
F1-12
Number of PG Gear
Teeth 1
(PG # Gear Teeth
1)
0~1000
1
0
—
x
-
A
-
-
F1-13
Number of PG Gear
Teeth 2
(PG # Gear Teeth
2)
0~1000
1
0
—
x
-
A
-
-
F1-14
PGO Detection
Time
(PGO Detect Time)
0~10.0
0.1s
2.0
—
x
-
A
-
A
Fu
nc
tio
n
F2
A
I-1
4
Se
tu
p
F2-01
AI-14B Card Input
Selection
(AI-14 Input Sel)
0, 1
1
0
0: (3-ch Individual)
1: (3ch Addition)
x
A
A
A
A
* When access level is BASIC (A1-03), constant is not displayed unless the option is connected.
Function
Parameter
No.
Name
(Digital Operator
Display)
Setting
Range
Setting
Unit
Factory
Setting
Remarks
(Digital Operator Display)
Change
during
Operation
o: Enabled
x: Disabled
Parameter Access Level
User
Setting
V/f
V/f
w/
PG
Open
Loop
Vector
Flux
Vector
Appendix
VS-616G5 Parameter List F Options