Section L: Protection Parameters

L2 Power Loss Ridethrough

In system applications requiring multiple drives with a common DC bus, KEB ride-through functions
differently. The inverter decelerates from the output frequency to the KEB frequency level, according
to the momentary power loss ridethough time (L2-02). The KEB frequency constant (L2-06) is set
according to the following equation:

This method is ideal when helper drives are being used on a film line, and a loss of power might cause
a line break. This method will allow synchronized deceleration for all of the common-bus drives, to
prevent speed deviation and thus a possible line break. If power is restored within the recovery time
(L2-02), then the inverter accelerates to the previous frequency reference according to acceleration
time 1 (C1-01).

KEB Ridethrough

ON

OFF

Output Frequency

L2-06

Fout (1 - )

L2-06

100%

L2-02

(common bus)

OFF

C1-01

Figure 50 KEB Ridethrough Timing Diagram

Multi-function Input Contact

(H1-__ = “65” or “66”)

KEB Frequency Level = Output Frequency (1 - )

L2-06