V/f

V/f w/PG Open Loop

Vector

Flux

Vector

66

VS-616G5 Programming Manual

Section F: Option Parameters

F1 PG Option Set-up

Setting Range:

0 to 50%

Factory Default:

115%

Sets the excessive speed deviation detection level as a percentage of maximum output frequency (E1-04).

Setting Range:

0.0 to 2.0s

Factory Default:

0.0s

Sets the elapsed time from when excessive speed deviation is detected to when a fault occurs.

A fault signal is output to stop operation after the deviation between speed reference and the motor
speed exceeds the set value of F1-10 and after the time set to F1-11 elapses. The stopping method is set
by F1-04. Also, detection is not activated while accelerating/decelerating or during torque control.

Setting Range:

0 to 1000

Factory Default:

0

Sets the number of teeth for each gear when gears are installed between the motor and the PG. When the
number of gear teeth is set, the motor revolutions per minute (rpm) are calculated as shown below.

This function is disabled when either F1-12 or F1-13 = “0”.

F1-10 PG Deviation Detection Level

PG Deviate Level

A

A

F1-11 PG Deviation Detection Time

PG Deviate Time

A

A

F1-12 Number of Teeth Gear 1

PG # Gear Teeth1

A

F1-13 Number of Teeth Gear 2

PG # Gear Teeth2

A

Figure 30 Overspeed Detection Timing Diagram

Speed Reference

OFF

ON

Motor Speed

F1-10

Speed Deviation

Fault Signal

F1-11

OFF

No. of Motor RPM’s =

No. of PG Output Pulses × 60

PG Pulses/Revolution (F1-01) ×

No. of Teeth Gear 2 (F1-13)

No. of Teeth Gear 1 (F1-12)