As a safety precaution the drive will not respond to a change in the run command when the digital
operator is being used to set or adjust parameters.This parameter will allow the drive to accept or
reject a change in the run command when the digital operator is being used to change or adjust param-
eters.

<1110>

Table 1:

B2

DC Braking

Setting Range:

0.0 to 10.0Hz

Factory Default:

0.5Hz

Sets the frequency at which DC injection braking (or initial excitation for flux vector control) starts, in
units of 0.1 Hz. When B2-01 < E1-09, DC injection braking starts from the minimum frequency refer-
ence (E1-09).

Setting Range:

0 to 100%

Factory Default:

50%

DC injection braking current is set as a percentage of inverter rated current. In flux vector control
mode, initial excitation is performed according to the motor no-load current set in E2-03. This param-
eter should not be set unnecessarily high or motor overexcitation may occur.

B1-08 Run Command Acceptance During Programming RUN CMD at PRG

A

A

A

A

Setting

Description

0

Run command is disabled when drive is in the programming mode. (factory default)

1

Run command is enabled when the drive is in the program mode

B2-01 DC Braking Frequency (Zero Speed Level)

DCInj Start Freq

B

B

B

B

B2-02 DC Braking Current

DCInj Current

B

B

B

-

Figure 5 DC Injection Braking at Starting

B2-01
DC Injection

B2-03

DC Injection Braking
Time at Start

Braking Frequency

Section B: Application Parameters

B2 DC Braking