VS-616G5 Programming Manual

89

· During Run (setting: “0”)

Closes when a run command is input, or when the inverter outputs voltage.

· Zero-speed (setting: “1”)

Closes when the inverter output frequency is less than the minimum output frequency (El-09) during
V/f control with PG feedback. Closes when the motor speed is less than the zero-speed level (B2-01)
during flux vector control.

5

Frequency detection 2

√

√

√

√

6

Inverter ready

√

√

√

√

7

DC bus undervoltage

√

√

√

√

8

Baseblock 1

√

√

√

√

9

Option reference

√

√

√

√

A

Remote operation

√

√

√

√

B

Torque detection 1 (N.O.)

√

√

√

√

C

Loss of reference

√

√

√

√

D

DB overheat

√

√

√

√

E

Fault

√

√

√

√

F

Not used

−

−

−

−

10

Minor fault

√

√

√

√

11

Reset command active

√

√

√

√

12

Timer output

√

√

√

√

13

Frequency agree 2

√

√

√

√

14

Desired frequency agree 2

√

√

√

√

15

Frequency detection 3

√

√

√

√

16

Frequency detection 4

√

√

√

√

17

Torque detection 1 (N.C.)

√

√

√

√

18

Torque detection 2 (N.O.)

√

√

√

√

19

Torque detection 2 (N.C.)

√

√

√

√

1A

Reverse direction

√

√

√

√

1B

Baseblock 2

√

√

√

√

1C

Motor 2 Selection

√

√

√

√

1D

Regenerating

−

−

−

√

1E

Restart enabled

√

√

√

√

1F

Overload (OL1)

√

√

√

√

20

OH pre-alarm

√

√

√

√

30

Current/torque limit

−

−

√

√

31

Speed limit

−

−

−

√

33

Zero servo completion

−

−

−

√

37

During run 2

√

√

√

√

H2-01

to 3

Setting

Function

Control Method (A1-02)

Reference

Page

V/f

V/f w/ PG

Open Loop

Vector

Flux Vector

Section H: Control Circuit Terminals

H2 Digital Outputs