Yaskawa VS-616G5 Series Revision F Programming Manual User Manual

Page 152

Advertising
background image

152

VS-616G5 Programming Manual

Pr

ot

ec

tio

n

Fu

nc

tio

n

L4

R

ef

er

en

ce

D

et

ec

tio

n

L4-01

Frequency
Detection Level
(Spd Agree Level)

0.0~

400.0

0.1Hz

0.0

x

B

B

B

B

L4-02

Frequency
Detection Width
(Spd Agree Width)

0.0~
20.0

0.1Hz

2.0

x

B

B

B

B

L4-03

Frequency
Detection Level ±
(Spd Agree Lvl ±)

–400.0 ~

+400.0

0.1Hz

0.0

x

A

A

A

A

L4-04

Frequency
Detection Width ±
(Spd Agree Wdth ±)

0.0~
20.0

0.1Hz

2.0

x

A

A

A

A

L4-05

Frequency Loss
Detection Selection
(Ref Loss Sel)

0, 1

1

0

0: (Stop)
1: (Run@ 80% PrevRef)

x

A

A

A

A

Fu

nc

tio

n

L5

F

au

lt

R

es

ta

rt

L5-01

Number of Auto
Restart Attempts
(Num of Restarts)

0~10

1

0

x

B

B

B

B

L5-02

Auto Restart
Operation Selection
(Restart Sel)

0, 1

1

0

0: (No Flt Relay)
1: (Flt Relay Active)

x

B

B

B

B

Fu

nc

tio

n

L6

T

or

qu

e

D

et

ec

tio

n

L6-01

Overtorque
Detection
Selection 1
(Torq Det 1 Sel)

0~4

1

0

0: (Disabled)
1: (@SpdAgree - Alm)
Detected during speed

agree only. Operation con-
tinues after detection and
OL3 flashes on display.

2: (At RUN - Alarm)
Overtorque detection during

running. Operation contin-
ues after detection and OL3
flashes on the display.

3: (@SpdAgree - Flt)
Detected during the speed

agree only. Inverter trips on
OL3, output is shut OFF.

4: (At RUN - Fault)
Detected during running,

and the inverter trips on
OL3. Output is shut OFF.

x

B

B

B

B

Function

Parameter

No.

Name

(Digital Operator

Display)

Setting

Range

Setting

Unit

Factory

Setting

Remarks

(Digital Operator Display)

Change

during

Operation

o: Enabled

x: Disabled

Parameter Access Level

User

Setting

V/f

V/f

w/

PG

Open

Loop

Vector

Flux

Vector

Appendix

VS-616G5 Parameter List L Protection

Advertising