Yaskawa VS-616G5 Series Revision F Programming Manual User Manual

Page 60

Advertising
background image

V/f

V/f w/PG Open Loop

Vector

Flux

Vector

60

VS-616G5 Programming Manual

Section E: Motor Parameters

E2 Motor 1 Set-up

Sets the motor leakage inductance in units of 0.1%. The default setting varies depending on the
inverter model setting (O2-04).

Setting Range:

0.00 to 1.00

Factory Default:

0.5

Sets the motor iron core saturation coefficient at 50% of the magnetic flux. This parameter is set auto-
matically during auto-tuning, so it does not need to be changed.

Setting Range:

0.00 to 1.00

Factory Default:

0.75

Sets the motor iron core saturation coefficient at 75% of the magnetic flux. This parameter is set auto-
matically during auto-tuning, so it does not need to be changed.

Setting Range:

0.0 to 10.0%

Factory Default:

0.0%

Sets the motor mechanical loss as a percentage of motor rated output power, in units of 0.1%.

Setting Range:

0 to 65535

Factory Default:

14 (Factory default depends on inverter capacity.)

This parameter sets the motor iron loss of the torque compensation.

E2-06 Leakage Inductance

Leak Inductance

A

A

E2-07 Core-Saturation Compensation Coefficient 1

Saturation Comp1

A

A

E2-08 Core-Saturation Compensation Coefficient 2

Saturation Comp2

A

A

E2-09 Motor Mechanical Loss

Mechanical Loss

A

E2-10 Motor Iron Loss Torque Compensation

<1110>

Tcomp Iron Loss

A

A