Yaskawa VS-616G5 Series Revision F Quick-Start User Manual

Page 100

Advertising
background image

VS-616G5 Installation & Quick-Start Manual

97

H1-04

Terminal 6
Selection
(Terminal 6 Sel)

00~77

1

4 (3)

(Note

15)

x

B

B

B

B

H1-05

Terminal 7
Selection
(Terminal 7 Sel)

00~77

1

6 (4)

(Note

15)

x

B

B

B

B

H1-06

Terminal 8
Selection
(Terminal 8 Sel)

00~77

1

8 (6)

(Note

15)

x

B

B

B

B

Note 15: Factory settings in the parentheses are values obtained at 3-wire initialization.

Te

rmi

nal

Fun

cti

on H

2 Di

gi

tal

O

utputs

H2-01

Multi-function Input
Terminal
9-10
(Terminal 9 Sel)

00~37

1

0

Multi-function output 1 (terminal

9, terminal 10)

(same as F5-01)

x

B

B

B

B

H2-02

Multi-function Input
Terminal 25
(Terminal 25 Sel)

00~37

1

1

Multi-function output 2 (terminal

25, terminal 27)

(same as F5-01)

x

B

B

B

B

H2-03

Multi-function Input
Terminal 26
(Terminal 26 Sel)

00~37

1

2

Multi-function output 3 (terminal

26, terminal 27)

(same as F5-01)

x

B

B

B

B

Func

tio

n H3 An

al

og

Inputs

H3-01

Signal Level Selec-
tion Terminal 13
(Term 13 Signal)

0, 1

1

0

0: (0 - 10 VDC)
1: (–10 +10 VDC)

x

B

B

B

B

H3-02

(Terminal 13 Gain)

0.0~

1000.0

0.1%

100.0

Frequency reference gain of AI-
14U, AI-14B (3ch addition
input), DI-08, and DI-16 is com-
mon.

o

B

B

B

B

H3-03

(Terminal 13 Bias)

–100.0

~

+100.0

0.1%

0.0

Frequency reference gain of AI-
14U, AI-14B (3ch addition
input), DI-08, and DI-16 is com-
mon.

o

B

B

B

B

H3-04

Terminal 16 Signal
Level Selection
(Term 16 Signal)

0, 1

1

0

0: (0 - 10 VDC)
1: (–10 +10 VDC)

x

B

B

B

B

H3-05

Terminal 16 Multi-
function Analog
Input
(Terminal 16 Sel)

0~1F

1

0

Multi-function analog input selec-

tion (terminal 16)

0: Auxiliary Reference

1: Frequency Gain

2: Frequency Bias

4: Voltage Bias

5: Accel/Decel Change

6: DC Brake Current

7: Overtorque Level

8: Stall Prevention Level

9: Reference Lower Limit

A: Jump Frequency

B: PID Feedback

C: PID Setpoint

D: Frequency Bias 2

10: Forward Torque Limit

11: Reverse Torque Limit

12: Regenerative Torque Limit

13: Torque reference

14: Torque Compensation

15: Forward/Reverse Torque Limit

1F: Not Used

x

B

B

B

B

Function

Parameter

No.

Name

(Digital Operator

Display)

Setting

Range

Setting

Unit

Factory

Setting

Remarks

(Digital Operator Display)

Change

during

Operation

o: Enabled

x: Disabled

Parameter Access Level

User

Setting

V/f

V/f

w/

PG

Open

Loop

Vector

Flux

Vector

Appendix

VS-616G5 Parameters

Advertising