230v, 460v – Yaskawa VS-616G5 Series Revision F Quick-Start User Manual

Page 9

Advertising
background image

VS-616G5 Installation & Quick-Start Manual

9

1.3 VS-616G5 SPECIFICATIONS

230V

460V

*

HP ratings based on NEMA 4-pole motor data. However, when sizing a drive to match a motor, use output current ratings.

#

For proper operation, the motor rated current must be less than or equal to the inverter rated current.

** kVA ratings are based on 200V, 400V, and 600V inputs respectively.

Inverter Model

CIMR-G5U

VS-616G5

20P4 20P7 21P5 22P2 23P7 25P5 27P5 2011 2015 2018 2022 2030 2037 2045 2055 2075

Outpu

t Char

ac

teri

st

ic

s

Nominal Motor Output
(HP) *

0.5

1

2

3

5

7.5

10

15

20

25

30

40

50

60

75

100

Capacity (kVA)**

1.2

2.3

3.0

4.2

6.7

9.5

13

19

24

30

37

50

61

70

85

110

Rated Output Current
(A)

#

3.2

6

8

11

17.5

25

33

49

64

80

96

130

160

183

224

300

Max. Voltage

3-Phase, 200/208/220/230V

(Proportional to input voltage)

Rated Output
Frequency

Up to 400 Hz available

Overload Capacity

150% Rated Current / 1 minute

Powe

r Supp

ly

Input Current (A)

3.9

7.2

9.6

13.2

21

30

40

59

77

88

106

143

176

202

247

330

Rated Voltage &
Frequency

3-Phase

200 to 230V, 50/60Hz

Voltage Fluctuation

+10%, -15%

Frequency Fluctuation

±5%

CIMR-G5U

40P440P741P542P243P744P045P547P5 4011 4015 4018 4022 4030 4037 4045 4055 4075 4110 4160 4185 4220 4300

Output C

hara

cter

is

tic

s

Nominal Motor Output
(HP) *

0.5

1

2

3

5

7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 350 500

Capacity (kVA)**

1.4 2.6 3.7 4.7 6.1 8.4 11 16 21 26 31 40 50 61 73 98 130 170 230 260 340 460

Rated Output Current
(A)

#

1.9 3.6 5.1 6.6 8.5 11.7 14.8 21 28.6 34 41 52 65 80 96 128 165 224 302 340 450 605

Max. Voltage

3-Phase, 380/400/415/440/460V

(Proportional to input voltage)

Rated Output
Frequency

Up to 400 Hz available

Overload Capacity

150% Rated Current / 1 minute

Power

Suppl

y

Input Current (A)

2.3 4.3 6.1 8 10.2 14 17.8 26 35 40 46 58 72 88 106 141 182 247 330 408 540 726

Rated Voltage &
Frequency

#

3-Phase

380 to 460V, 50/60Hz

Voltage Fluctuation

+10%, -15%

Frequency Fluctuation

±5%

Chapter 1 - Receiving & Installation

Specifications

Advertising