92

VS-616G5 Installation & Quick-Start Manual

Group

E Motor

Func

tion E5 Mo

tor Set

up 2

E5-01

Motor 2 Rated
Current
(Motor Rated FLA)

0.00~

1500.0

0.1A*

1.9**

* Setting unit is 0.01A for mod-
els of 7.5 kW or less.

** Factory setting differs
depending on inverter capacity
(02-04).

x

A

(Note

14)

A

(Note

14)

A

(Note

14)

A

(Note

14)

E5-02

Motor 2 Rated Slip
(Motor Rated Slip)

0.00~
20.00

0.01Hz 2.90**

x

A

(Note

14)

A

(Note

14)

A

(Note

14)

A

(Note

14)

E5-03

Motor 2 No-load
Current
(No-Load Current)

0.00~

1500.0

0.01A* 1.20**

x

A

(Note

14)

A

(Note

14)

A

(Note

14)

A

(Note

14)

E5-04

Motor 2 Number of
poles
(Motor 2 # Poles)

2~48

1 pole

4

x

-

(Note

14)

A

(Note

14)

-

(Note

14)

A

(Note

14)

E5-05

Motor 2 Line-to-line
Resistor
(Motor 2 term
Ohms)

0.000~
65.000

0.001

W

9.842**

x

A

(Note

14)

A

(Note

14)

A

(Note

14)

A

(Note

14)

E5-06

Motor 2 Leak Induc-
tance
(Motor 2 Leak)

0.0~
30.0

0.1%

18.2**

x

A

(Note

14)

-

(Note

41)

A

(Note

14)

A

(Note

14)

Note 13: This value is for the 200V class. For 400V class, the value is twice that of 200V class. For 575V class, modify the values by 575/200
Note 14: Control mode is determined by E3-01.

Gr

oup F

Opti

on

s

*

Func

tion

F1 PG Opti

on Set

up

F1-01

PG Constant
(PG Pulses/Rev)

0~

60000

1

600*

*When 02-09=1 (USA), 2
(EUR.), factory setting is 1024

x

-

Q

-

Q

F1-02

Operation Selec-
tion at PG Open
Circuit
(PG Fdbk Loss Sel)

0~3

1

1

0: (Ramp to Stop)
1: (Coast to Stop)
2: (Fast-Stop)
3: (Alarm Only)

x

-

B

-

B

F1-03

Operation Selec-
tion at Overspeed
(PG Overspeed
Sel)

0~3

1

1

0: (Ramp to Stop)
1: (Coast to Stop)
2: (Fast-Stop)
3: (Alarm Only)

x

-

B

-

B

F1-04

Operation Selec-
tion at Deviation
(PG Deviation Sel)

0~3

1

3

0: (Ramp to Stop)
1: (Coast to Stop)
2: (Fast-Stop)
3: (Alarm Only)

x

-

B

-

B

F1-05

PG Rotation
(PG Rotation Sel)

0, 1

1

0

0: Counter-clockwise
(Fwd = C.C.W.)
1: Clockwise
(Fwd = C.W.)

x

-

B

-

B

F1-06

PG Division Rate
PG --Pulse monitor
(PG Output Ratio)

1~132

1

1

Effective only when control cir-
cuit board PG-B2 is used.

x

-

B

-

B

F1-07

Integral Value
during Accel/decel
Enable/disable
(PG Ramp PI/I Sel)

0, 1

1

0

0: (Disabled)
1: (Enabled)

x

-

B

-

-

F1-08

Overspeed
Detection Level
(PG Overspd Level)

0~120

1%

115

x

-

A

-

A

* When access level is BASIC (A1-03), constant is not displayed unless the option is connected.

Function

Parameter

No.

Name

(Digital Operator

Display)

Setting

Range

Setting

Unit

Factory

Setting

Remarks

(Digital Operator Display)

Change

during

Operation

o: Enabled

x: Disabled

Parameter Access Level

User

Setting

V/f

V/f

w/

PG

Open

Loop

Vector

Flux

Vector

Appendix

VS-616G5 Parameters