Yaskawa VS-616G5 Series Revision F Quick-Start User Manual

Page 45

Advertising
background image

42

VS-616G5 Installation & Quick-Start Manual

Operation by Control Circuit Terminal Signal
The diagram below shows a typical operation profile using the control circuit terminal signals.

Typical Operation Example by Control Circuit Terminal Signal

Description

Key Sequence

Digital Operator Display

Figure 16 Operation Sequence by Control Circuit Terminal Signal

Power ON

Frequency Setting

Operation

Forward

60Hz

Stop

1

2

3

4

!

Power ON

· Displays frequency reference value.

REMOTE mode is preset at the factory.

Output Frequency Display

· Switch to output frequency display.

Forward Jog Run (6Hz)

· Close between control circuit terminals 1 &

11, and 7 & 11 closed to perform JOG run.
Run & FWD LEDs illuminate.

· Open between terminals 1 & 11, and 7 & 11

after verifying JOG operation

"

Frequency Setting

· Input frequency reference via terminal 13

(voltage) or 14 (voltage/current) and verify
the input value with the digital operator.

Output Frequency Display

· Select output frequency monitor display.

#

Forward Run

· Close between terminals 1 & 11 to perform

forward run.

$

Stop

· Open between terminals 1 & 11 to stop

operation. Stop LED illuminates.

Frequency Ref

REMOTE LED (SEQ, REF) ON

U1-01 = 0.00 Hz

Output Freq

U1-02 = 0.00 Hz

Output Freq

U1-02 = 60.00 Hz

Output Freq

U1-02 = 0.00 Hz

Output Freq

U1-02 = 6.00 Hz

Frequency Ref

U1-01 = 60.00 Hz

Output Freq

U1-02 = 0.00 Hz

Chapter 2 - Operation

Trial Operation