Yaskawa VS-616G5 Series Revision F Quick-Start User Manual

Page 101

Advertising
background image

98

VS-616G5 Installation & Quick-Start Manual

Te

rmi

nal

Ana

log Inputs

H3-06

(Terminal 16 Gain)

0.0~

1000.0

0.1%

100.0

o

B

B

B

B

H3-07

(Terminal 16 Bias)

–100.0

~ +100.0

0.1%

0.0

o

B

B

B

B

H3-08

Signal Level
Selection Terminal
14
(Term 14 Signal)

0, 1, 2

1

2

0: (0 - 10 VDC)
1: (–10 +10 VDC)
2: (4 - 20 mA)

x

A

A

A

A

H3-09

Multi-function
Analog Input
Terminal 14
(Terminal 14 Sel)

1~1F

1

1F

The function choices for terminal

14 are the same as the choices

for terminal 16 [ see H3-05},

except that [setting 0] “Auxiliary

Reference” is not available.

x

A

A

A

A

H3-10

Terminal 14 Gain
(Terminal 14 Gain)

0.0~

1000.0

0.1%

100.0

o

A

A

A

A

H3-11

Terminal 14 Bias
(Terminal 14 Bias)

–100.0

~

+100.0

0.1%

0.0

o

A

A

A

A

H3-12

Analog Input Filter
Time Constant
(Filter Avg Time)

0.00~

2.00

0.01s

0.00

x

A

A

A

A

Function

Parameter

No.

Name

(Digital Operator

Display)

Setting

Range

Setting

Unit

Factory

Setting

Remarks

(Digital Operator Display)

Change

during

Operation

o: Enabled

x: Disabled

Parameter Access Level

User

Setting

V/f

V/f

w/

PG

Open

Loop

Vector

Flux

Vector

Appendix

VS-616G5 Parameters

Advertising