Yaskawa VS-616G5 Series Revision F Quick-Start User Manual

Page 69

Advertising
background image

66

VS-616G5 Installation & Quick-Start Manual

EF3

External Fault 3

External fault at
terminal 3

Fault occurred in the external control
circuit.

Check the condition of the
input terminal. If the LED
lights when terminal is not
connected, then the inverter
requires repair.

A

EF4

External Fault 4

External fault at
terminal 4

Fault occurred in the external control
circuit.

Check the condition of the
input terminal. If the LED
lights when terminal is not
connected, then the inverter
requires repair.

B

EF5

External Fault 5

External fault at
terminal 5

EF6

External Fault 6

External fault at
terminal 6

EF7

External Fault 7

External fault at
terminal 7

EF8

External Fault 8

External fault at
terminal 8

OPE01

kVA Selection

kVA setting error
(OPE01)

Inverter kVA setting error.

Check and set the parameter
data (O2-04).

C

OPE02

Limit

Parameter setting
range error (OPE02)

Parameter data is out of range.

Check the parameter data
settings.

C

OPE03

Terminal

Multi-function input
setting error (OPE03)

·Multi-function input settings in H1-01

to H1-06 are not in ascending order.

·Or, set values other than “F” are over-

lapping.

Check the function selection.

C

OPE10

V/f

V/f data setting error
(E1-04 to E1-10)

V/f data is set such that the following
equation is not satisfied:
E1-04

E1-06 > E1-07 E1-09

Check the parameter data
settings.

C

OPE11

FC/ On-Dly

Parameter setting error

When one of the following setting
errors occurs:
·Carrier frequency upper limit

(C6-01) > 5kHz, and Carrier
frequency lower limit (C6-02)

≤ 5kHz

·Carrier frequency proportional gain

(C6-03) > 6 and (C6-01) < (C6-02)

Check the parameter data
settings.

C

ERR

EEPROM R/W Err

EEPROM writing fault
(ERR)

EEPROM internal data did not match
when initializing the parameter.

Replace the control board.

B

CALL

Serial Com Call

SI-B transmission error

Control data was not received correctly
when power supply was turned ON.

Check transmission devices
and transmission signals.

C

CE

Memobus Com Err

Transmission error

Control data was not received correctly
when power supply was turned ON.

Check transmission devices
and transmission signals.

A

Fault Display

Name

Description

Corrective Action

Class

Chapter 4 - Diagnostics

Alarm & Fault Displays