Custom V/f Pattern
Set up a custom V/f pattern by setting parameter E1-03 to “F”, and then setting the values in parame-
ters E1-04 to E1-10.

* For 460V class units, the value is twice that of 230V class units. For 575V class units the value is 2.5 times the 230V value.

Increasing the voltage in the V/f pattern increases motor torque. However,

when setting a custom

V/f pattern, increase the voltage gradually while monitoring the motor current, to prevent

:

· Inverter fault trips as a result of motor overexcitation
· Motor overheat or excessive vibration

V/f

Control

V/f

w/ PG

Open Loop

Vector

Flux

Vector

E1-04 Maximum Frequency

Max Frequency

E1-05 Maximum Voltage

Max Voltage

E1-06 Maximum Voltage Output Frequency

Base Frequency

E1-07 Middle Output Frequency

Mid Frequency A

E1-08 Middle Output Voltage

Mid Voltage A

E1-09 Minimum Output Frequency

Min Frequency

E1-10 Minimum Output Voltage

Min Voltage

E1-13 Motor Base Voltage

Base Voltage

Parameter

No.

Name

Unit

Setting Range

Factory

Default

E1-04

Maximum output frequency

0.1 Hz

50.0 to 400 Hz

60.0 Hz

E1-05

Maximum voltage

0.1 V

0.1 to 255 V *

230 V *

E1-06

Maximum voltage output frequency
(base frequency)

0.1 Hz

0.2 to 400 Hz

60.0 Hz

E1-07

Mid. output frequency

0.1 Hz

0.1 to 399 Hz

3.0 Hz

E1-08

Mid. output frequency voltage

0.1 V

0.1 to 255 V *

17.2 V *

E1-09

Minimum output frequency

0.1 Hz

0.1 to 10.0 Hz

1.5 Hz

E1-10

Minimum output frequency voltage

0.1 V

0.1 to 50.0 V *

10.3 V *

Be sure to satisfy the following conditions
for setting parameters E1-04 to E1-10:
E1-09

E1-07 < E1-06E1-04

0

E1-09 E1-07 E1-06

E1-04

Frequency

Voltage

E1-10

E1-08

E1-05

Figure 23 Custom V/f Pattern Setting

Chapter 3 - Quick-Start Programming

Programming Menu