VS-616G5 Installation & Quick-Start Manual

Pro

tec

tion

Func

tion L8 H

ardw

are

Protec

tion

L8-01

Internal DB
Resistor
Protection Selection
(DB Resistor Prot)

0, 1

1

0

0: (Not Provided)
1: (Provided)

x

B

B

B

B

L8-02

Overheat Pre-alarm
Level
(OH Pre-Alarm Lvl)

1 deg C 95 C*

x

A

A

A

A

L8-03

Operation Selec-
tion after OH Pre-
alarm
(OH Pre-Alarm Sel)

0~3

1

3

0: (Ramp to Stop) using C1-02
1: (Coast to Stop)
2: (Fast-Stop) using C1-09
3: (Alarm Only) display flashes
OH Heatsink Ovrtemp

x

A

A

A

A

L8-05

Input Phase Loss
Protection
(PH Loss In Sel)

0, 1

1

0

0: (Disabled)
1: (Enabled)

x

A

A

A

A

L8-07

Output Phase Loss
Protection
(PH Loss Out Sel)

0, 1

1

0*

0: (Disabled)
1: (Enabled)
*When 02-09=1, the factory

default setting is 1.

x

A

A

A

A

Prot

ec

tion

Func

tion L8 H

ardw

are

Protec

tion

L8-10

Short-circuit
Protection Selection
(Ground Fault Sel)

0, 1

1

1

0: (Disabled)
1: (Enabled)

x

A

A

A

A

L8-17

IGBT Protection
Selection at Low
Frequency
(Prtct@L - Spd)

0, 1

1

1*

0: Conventional
1: (Lower fc)
Carrier frequency is

decreased when fout

10Hz and the load is >
100% iac.

2: (Short term OL2)
OL occurs after 2 seconds

during low speed [fout

6Hz] current limit.

3: (I-Limit=150%)
Current limit is set to 150%

of the inverter rated current.
< G5 + > Addition

* When 02-09=1 factory set-

ting is 1.

* When 02-09=2 factory set-

ting is 2.

x

A

A

A

-

L8-19

<1110>

OL2 Characteris-
tics Selection at
Low Speed
(OL2 Chara@L-
Spd)

0, 1

1

0

0: (Disabled)
Low frequency OL disabled
1: (Enabled)
Low frequency OL enabled

x

A

A

A

A

Function

Parameter

No.

Name

(Digital Operator

Display)

Setting

Range

Setting

Unit

Factory

Setting

Remarks

(Digital Operator Display)

Change

during

Operation

o: Enabled

x: Disabled

Parameter Access Level

User

Setting

V/f

V/f

w/

PG

Open

Loop

Vector

Flux

Vector

50~130

*Factory setting depends on
inverter model [02-04].

Appendix

VS-616G5 Parameters