VS-616G5 Installation & Quick-Start Manual

85

G

roup C

T

uni

ng

Fu

nc

tion

C6 Ca

rri

er

Fr

equen

cy

C6-01

Carrier Frequency
Upper Limit
(Carrier Freq Max)

0.4~

15.0**

0.1 kHz 15.0** When control mode is vector

control (A1-02=2, 3), the setting
range of C6-01 and C6-02 is
2.0 ~15.0.
** Setting range and factory
setting differ depending on
inverter capacity.

x

B

B

B

B

C6-02

Carrier Frequency
Lower Limit (Car-
rier Freq Min)

0.4~
15.0

0.1 kHz 15.0**

x

A

A

-

-

C6-03

Carrier Frequency
Proportional Gain
(Carrier Freq Gain)

00~99**

1

00**

x

A

A

-

-

Fu

nc

tion C7 Hun

tin

g

Pre

ven

tion

C7-01

Hunting Prevention
Selection
(Hunt Prev Select)

0, 1

1

1

0: Disabled
1: Enabled

x

A

A

-

-

C7-02

Hunting Prevention
Gain
(Hunt Prev Gain)

0.00~

2.50

0.01

1.00

x

A

A

-

-

G

roup C

T

uni

ng

Fun

cti

on C

8 Fa

ct

or

y T

uni

ng

C8-08

AFR Gain
(AFR Gain)

0.00~
10.00

0.01

1.00

x

-

-

A

-

C8-09

AFR Time Constant
(AFR Time)

0~2000 1

ms

50

x

-

-

A

-

C8-30

<1110>

Carrier
Frequency
Selection during
Auto-tuning
(Carrier in tune)

0~2

1

0

0: Carrier frequency is

2 kHz.

1: Carrier frequency depends

on C6-01.

2: Carrier frequency is

5 kHz. (185~300 kW: 2.5
kHz)

x

-

-

A

A

Function

Parameter

No.

Name

(Digital Operator

Display)

Setting

Range

Setting

Unit

Factory

Setting

Remarks

(Digital Operator Display)

Change

during

Operation

o: Enabled

x: Disabled

Parameter Access Level

User

Setting

V/f

V/f

w/

PG

Open

Loop

Vector

Flux

Vector

Appendix

VS-616G5 Parameters