58

VS-616G5 Installation & Quick-Start Manual

Sets the motor rated current in units of 0.01A for inverter sizes 7.5kW and smaller; 0.1A for sizes
11kW and larger. This setting varies depending on the inverter model setting (O2-04).

Setting range:

0.00 to 20.00Hz

Sets the motor rated slip frequency in units of 0.01Hz. This setting varies depending on the motor. Use
the following equation to calculate the motor rated slip frequency:

Sets the motor no-load current in units of 0.01A for inverter sizes 7.5kW and smaller; 0.1A for sizes
11kW and larger. This setting varies depending on the inverter model setting (O2-04).

Setting Range:

2 to 48 poles

Factory Default:

4 poles

Sets the number of motor poles.

Setting Range:

0 to 60000

Factory Default:

1024

Sets the encoder pulse count (per revolution) for the closed loop control modes (VF w/PG and Flux
Vector).

V/f

Control

V/f

w/ PG

Open Loop

Vector

Flux

Vector

E2-01 Motor Rated Current

Motor Rated FLA

V/f

Control

V/f

w/ PG

Open Loop

Vector

Flux

Vector

E2-02 Motor Rated Slip Frequency

Motor Rated Slip

V/f

Control

V/f

w/ PG

Open Loop

Vector

Flux

Vector

E2-03 Motor No-Load Current

No-Load Current

V/f

Control

V/f

w/ PG

Open Loop

Vector

Flux

Vector

E2-04 Number of Motor Poles

Number of Poles

V/f

Control

V/f

w/ PG

Open Loop

Vector

Flux

Vector

F1-04 PG Constant

PG Pulses/Rev

where:

fs f

N P

(

)

120

-----------------

=

f : slip frequency (Hz)

f : motor rated frequency (Hz)
N : motor rated speed (rpm)
P : number of motor poles

s

Chapter 3 - Quick-Start Programming

Programming Menu