Yaskawa VS-616G5 Series Revision F Quick-Start User Manual

Page 103

Advertising
background image

100

VS-616G5 Installation & Quick-Start Manual

Gro

up H T

er

m

in

al

F

unc

tion

Functi

on

H5 Ser

ial

C

om Setup

MODBUS C

ommuni

cati

on

H5-01

Station Address
(Serial Comm Adr)

0~20

1

1F

x

A

A

A

A

H5-02

Communication
Speed Selection
(Serial Baud Rate)

0~4

0

3

0 : (1200 Baud)
1 : (2400 Baud)
2 : (4800 Baud)
3 : (9600 Baud)
4 : (19200 Baud)

<1110>

x

A

A

A

A

H5-03

Communication
Parity Selection
(Serial Com Sel)

0, 1, 2

1

0

0 : (No Parity)
1 : (Even Parity)
2 : (Odd Parity)

x

A

A

A

A

H5-04

Stopping Method
After Communica-
tion Error
(Serial Fault Sel)

0~3

1

3

0: (Ramp to Stop)
1: (Coast to Stop)
2: (Fast - Stop)
3: (Alarm Only)

x

A

A

A

A

H5-05

Timeover Detection
(Serial Flt Dtct)

0, 1

1

1

0 : (Disabled)
1 : (Enabled)

x

A

A

A

A

Prot

ec

tion

Func

tion L1

Motor

O

ver

lo

ad

L1-01

Motor Protection
Selection
(MOL Fault Select )

0, 1

1

1

0: (Disabled)
1: (Coast to Stop)

x

B

B

B

B

L1-02

Motor Protection
Time Constant
(MOL Time Const)

0.1~5.0

min.

0.1 min.

1.0

When O2-09=1 [American
Spec] the setting range is
0.1~20min. The factory default
setting then becomes 8 min.
8 min. is the operation time
from a cold start.

x

B

B

B

B

Protec

tion

Fu

nc

tion

L2 Powe

r Los

s Ri

de T

hro

ugh

L2-01

Momentary Power
Loss Detection
(PwrL Selection)

0, 1, 2

1

0

0 : (Disabled)
1 : Power loss ride through
(PwrL RideThru t)
2 : (CPU Power Active)

x

B

B

B

B

L2--02

Momentary Power
Loss Ride Through
(PwrL Ridethru t)

0.0~2.0

0.1s

0.7**

** Factory setting differs
depending on inverter capacity
(02-04).

x

B

B

B

B

L2-03

Min. Baseblock
Time
(PwrL Baseblock t)

0.1~5.0

0.1s

0.5*

* Factory setting differs
depending on inverter capacity.

Lower limit of setting range is
changed from 0 to 0.1.

<1110>

x

B

B

B

B

L2-04

Voltage Recovery
Time
(PwrL V/F Ramp t)

0.0~5.0

0.1s

0.3*

* Factory setting differs
depending on inverter capacity
(02-04).

x

A

A

A

A

L2-05

Undervoltage
Detection Level
(PUV Det Level)

150~

210

1V

190*

*Voltage Class
200V class=190V Det level
400V class=190V x 2= 380V level
575V class=190x575/200=546 level

x

A

A

A

A

L2-06

KEB Deceleration
Rate
(KEB Frequency)

0.0~

100.0

0.1%

0.0

x

A

A

A

A

Function

Parameter

No.

Name

(Digital Operator

Display)

Setting

Range

Setting

Unit

Factory

Setting

Remarks

(Digital Operator Display)

Change

during

Operation

o: Enabled

x: Disabled

Parameter Access Level

User

Setting

V/f

V/f

w/

PG

Open

Loop

Vector

Flux

Vector

Appendix

VS-616G5 Parameters