Yaskawa VS-616G5 Series Revision F Quick-Start User Manual

Page 96

Advertising
background image

VS-616G5 Installation & Quick-Start Manual

93

Gr

oup F

Opti

on

s *

Functi

on

F

1 PG Opti

on Setu

p

F1-09

Overspeed
Detection Delay
Time
(PG Overspd Time)

0.0~2.0

0.1s

0.0*

* When A1-02=1 [V/f w/PG] fac-
tory setting is 1.0. When A1-
02=3 [ Flux Vector] factory set-
ting is 0.0.

x

-

A

-

A

F1-10

Excessive Speed
Deviation Detection
Level
(PG Deviate Level)

0~50

1%

10

x

-

A

-

A

F1-11

Excessive Speed
Deviation detection
Delay Time
(PG Deviate Time)

0.0~
10.0

0.1s 0.5

x

-

A

-

A

F1-12

Number of PG Gear
Teeth 1
(PG # Gear Teeth
1)

0~1000

1

0

x

-

A

-

-

F1-13

Number of PG Gear
Teeth 2
(PG # Gear Teeth
2)

0~1000

1

0

x

-

A

-

-

F1-14

PGO Detection
Time
(PGO Detect Time)

0~10.0

0.1s

2.0

x

-

A

-

A

Fun

cti

on F

2 AI-

14 Setup

F2-01

AI-14B Card Input
Selection
(AI-14 Input Sel)

0, 1

1

0

0: (3-ch Individual)
1: (3ch Addition)

x

A

A

A

A

* When access level is BASIC (A1-03), constant is not displayed unless the option is connected.

Function

Parameter

No.

Name

(Digital Operator

Display)

Setting

Range

Setting

Unit

Factory

Setting

Remarks

(Digital Operator Display)

Change

during

Operation

o: Enabled

x: Disabled

Parameter Access Level

User

Setting

V/f

V/f

w/

PG

Open

Loop

Vector

Flux

Vector

Appendix

VS-616G5 Parameters