50

VS-616G5 Installation & Quick-Start Manual

· DC Injection Braking Stop (B1-03 = “2”)

Upon removal of the FWD (REV) run command, the motor brakes to stop, according to the DC injec-
tion braking time at stop set in B2-04. If this value is set to “0” (factory default), DC injection braking
is disabled, and the motor coasts to stop. When choosing this function, note that the actual stop time
from maximum frequency is the time set in B2-04 multiplied by 10 (see the figure above). This stop-
ping method is disabled during flux vector control.

· Coast to Stop with Timer 1 (B1-03 = “3”)

After a stop command is given, a run command is not accepted while the coast to stop timer C1-02
elapses (same as Decel Time 1). After the timer runs out, another run command must be given for the
inverter to begin acceleration. This stopping method is disabled during flux vector control.

Output Frequency

Run Command

ON

OFF

DC injection Braking Time

at Stop (B2-04)

Factory Default: 0.0s

Minimum Baseblock Time (L2-03)

Factory Default: 0.5s

Inverter Output OFF during

Figure 21 Stopping Method - DC Injection Braking Stop

DC injection Braking Time

at Stop (B2-04)

DC injection

Braking Time

B2-04 x 10

F

max

(E1-04)

F

out

Output Frequency

Coasting

Decel Time 1
(C1-02)

Accel Time 1
(C1-01)

Time

ON

ON

ON

FWD (REV)
Run Command

Run Command Disabled

Figure 22 Stopping Method - Coast to Stop w/ Timer

Chapter 3 - Quick-Start Programming

Programming Menu