88

VS-616G5 Installation & Quick-Start Manual

Gr

oup E Mo

tor

Functi

on

E1 V/F

Pattern

E1-01

Input Voltage
Setting
(Input Voltage)

155~

255

(Note

13)

1 V

200

(Note

13)

¹When 02-09=1 [USA], the
value is 1.15 times of Japanese
spec., which is 230/200

x

Q

Q

Q

Q

E1-02

Motor Selection
(Motor Selection)

0, 1, 2

1

0

0: (Std Fan-Cooled)
1: (Std Blower-Cooled)
2: (Vector Motor)

<1110>

x

Q

Q

Q

Q

E1-03

V/f Pattern
Selection
(V/F Selection)

00~0F

1

0F

V/f pattern selection

0: 50Hz

1: 60Hz Saturation

2: 50Hz Saturation

3: 72Hz

4: 50Hz Variable Torque 1

5: 50Hz Variable Torque 1

6: 60Hz Variable Torque 1

7: 60Hz Variable Torque 2

8: 50Hz High Starting Torque 1

9: 50Hz High Starting Torque 2

A: 60Hz High Starting Torque 1

B: 60Hz High Starting Torque 2

C: 90Hz

D: 120Hz

E: 180Hz

F: User-defined V/f pattern

x

Q

Q

Q

Q

E1-04

Max. Output
Frequency
(Max Frequency)

40.0~40

0.0

0.1Hz

60.0*

(Note

13)

*Factory setting differs depend-
ing on the inverter capacity 02-
04.
When 02-09=2 [EUR.], the
value is 50.0Hz.

x

Q

Q

Q

Q

E1-05

Max. Voltage
(Max Voltage)

0.0~

255.0
(Note

13)

0.1 V

200.0
(Note

13)*

*Factory setting differs depend-
ing on the inverter capacity (02-
04).

When 02-09=1 (USA), the
value is 1.15 times of Japanese
spec., which is 230/200

x

Q

Q

Q

Q

Note 13: This value is for the 200V class. For 400V class, the value is twice that of 200V class. For 575V class, then modify the values by 575/200

Function

Parameter

No.

Name

(Digital Operator

Display)

Setting

Range

Setting

Unit

Factory

Setting

Remarks

(Digital Operator Display)

Change

during

Operation

o: Enabled

x: Disabled

Parameter Access Level

User

Setting

V/f

V/f

w/

PG

Open

Loop

Vector

Flux

Vector

Appendix

VS-616G5 Parameters