Yaskawa VS-616G5 Series Revision F Quick-Start User Manual

Page 90

Advertising
background image

VS-616G5 Installation & Quick-Start Manual

87

G

roup d

Refer

enc

e

Fun

cti

on d

4 Sequen

ce

D4-01

Frequency Refer-
ence Hold Function
Selection
(MOP Ref Memory)

0, 1

1

0

0: (Disabled)

No hold frequency is memo-
rized.

1: (Enabled)

Hold frequency is memo-
rized.

x

A

A

A

A

D4-02

±Speed Limits
(Trim Control Lvl)

0~100

1%

25*

*When 02-09=1 [USA], the unit
is 10%. <24>

x

A

A

A

A

Func

tion d5 T

or

que C

ontro

l

D5-01

Torque Control
Selection
(Torq Control Sel)

0, 1

1

0

0: (Speed Control)
1: (Torque Control)

x

-

-

-

A

D5-02

Torque Reference
Delay Time
(Torque Ref Filter)

0~1000

1 ms

0

x

-

-

-

A

D5-03

Speed Limit
Selection
(Speed Limit Sel)

1, 2

1

1

1: (Analog Input) terminal 13,

14

2: (Program Setting)

x

-

-

-

A

D5-04

Speed Limit
(Speed Lmt Value)

–120 ~

+120

1%

0

x

-

-

-

A

D5-05

Speed Limit Bias
(Speed Lmt Bias)

0~120

1%

10

x

-

-

-

A

D5-06

Speed/torque
Control Switching
Timer
(Ref Hold Time)

0~1000

1 ms

0

x

-

-

-

A

Function

Parameter

No.

Name

(Digital Operator

Display)

Setting

Range

Setting

Unit

Factory

Setting

Remarks

(Digital Operator Display)

Change

during

Operation

o: Enabled

x: Disabled

Parameter Access Level

User

Setting

V/f

V/f

w/

PG

Open

Loop

Vector

Flux

Vector

Appendix

VS-616G5 Parameters