Parameters

Conceptual Relation between Output Power and Temperature

Below graph represents conceptual relation between inverter output power and heat sink temperature. The
output power is reduced in proportion to heat sink temperature but keep in mind that the power derating is
activated at 90°C and deactivated at 70°C (The activation/deactivation temperature can be tunable by param-
eter).

Figure 79: Relation between output power and temperature

Tab

Number Parameter

Min

Max

Default Value

PV Array

38

Power Derating Enable

0

1

1

39

Power Derating Enable Temperature

50

100

90

40

Power Derating Disable Temperature

40

90

70

41

Power Derating Disable Reference
Temperature

45

95

80

42

Power Derating P gain

0

10

2

Table 22: Related Parameters (ex. BP1000 Model)