KACO blueplanet 750 - 1000 kVA User Manual
Page 101

KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0
Page 101
Parameters
Conceptual Relation between Output Power and Temperature
Below graph represents conceptual relation between inverter output power and heat sink temperature. The
output power is reduced in proportion to heat sink temperature but keep in mind that the power derating is
activated at 90°C and deactivated at 70°C (The activation/deactivation temperature can be tunable by param-
eter).
Figure 79: Relation between output power and temperature
Tab
Number Parameter
Min
Max
Default Value
PV Array
38
Power Derating Enable
0
1
1
39
Power Derating Enable Temperature
50
100
90
40
Power Derating Disable Temperature
40
90
70
41
Power Derating Disable Reference
Temperature
45
95
80
42
Power Derating P gain
0
10
2
Table 22: Related Parameters (ex. BP1000 Model)