KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0

Faults and Warnings

Code Message

Warning Description

Possible problem and Solution(s)

41

Flash Memory
Failure

C6000 DSP program flash
memory failure in XCU (main
control) board

Possible problem
• Internal C6000 error
Solution(s)
• Change the PCB module

42

FPGA Failure

FPGA failure in XCU (main
control) board

Possible problem
• Internal FPGA error
Solution(s)
• Change the PCB module

43

DSP28x Failure

F2000 DSP failure in XCU (main
control) board

Possible problem
• Internal F2000 error
Solution(s)
• Change the PCB module

44

ADC Failure

ADC block failure in XCU (main
control) board

Possible problem
• Internal Analog to Digital converter
error
Solution(s)
• Change the PCB module

45

NVSRAM Failure

NVSRAM failure in XCU (main
control) board or invalid param-
eter

Possible problem
• Internal NVSRAM error
• Invalid parameter
Solution(s)
• Initialize the parameter menu setting in
the GUI
• Change the PCB module

47

CAN Failure

CAN bus communication failure Possible problem

• CAN bus communication Failure
Solution(s)
• Check the CAN bus Connection
• Check the CAN bus terminal registers

50

Emergency Stop

The door is open/The emer-
gency stop botton is pressed

Possible problem
• Front door is open
• Broken or out of alignment door switch
Solution(s)
• Close the door
• Align or replace door switch

Table 8: Fault