KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0

Page 119

Parameters

8.2.9 Protection

If the function of {FRT Enable} is not active, BP Series TL3 OD inverter parameters for abnormal grid is as follows.

Grid Under Frequency

Figure 97: Grid under frequency

1. f < f

rated

- 2Hz, t > 10s → Grid Under Frequency Level 1 Fault

2. f < f

rated

- 2.5Hz, t > 100ms → Grid Under Frequency Level 2 Fault

Grid Over Frequency

Figure 98: Grid over frequency

1. f > f

rated

+ 0.2Hz, t > 100ms → Grid Over Frequency Fault

2. It disables Grid Over Frequency Level 2 and Grid Over Frequency Level 2.