Grid parameters – KACO blueplanet 750 - 1000 kVA User Manual
Page 80

Page 80
KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0
Parameters
Grid Parameters
Parameters
Min
Max
Unit
Descriptions
Rated Grid Voltage 208
400
V
Rated value of the grid voltage
Rated Grid
Frequency
50
60
Hz
Rated value of the grid frequency
Grid Over Voltage
Level 1
105
130
%
Upper limit expressed as a percentage of the rated
grid voltage for grid overvoltage level 1
Grid Under Voltage
Level 1
75
100
%
Lower limit expressed as a percentage of the rated
grid voltage for grid under voltage Level 1
Grid Over Frequency
Level 1
0
3
Hz
Upper limit for grid over frequency level 1
Grid Under
Frequency Level 1
0
3
Hz
Lower limit for grid under frequency level 1
Frequency Depend-
ant Power Reduc-
tion Mode
0
2
-
Power reduction function dependant on frequency
rise
0: Disable
1: Enable
Power Gradient
Mode
0
5
-
Power gradient function when inverter start
0: Disable
1: Activated when connected to grid after fault
(Germany Medium Voltage Requirements)
2: Activated according to VDE-AR-N 4105
(Germany Low Voltage Requirements)
3: Activated whenever connected to grid
(Italy TERNA Grid Code)
Power Gradient
Ramp
0
600
sec
Ramp time for power gradient
Time Shift
0
6000
sec
Delay time for inverter start
Gate-way Enable
0
1
-
Reserved
Grid Level 2
Protection Enable
0
1
-
Grid level 2 protection function
0: Disable
1: Enable
Grid Over Voltage
Level 2
105
130
%
Upper limit expressed as a percentage of the rated
grid voltage for grid overvoltage level 2
Grid Under Voltage
Level 2
15
100
%
Lower limit expressed as a percentage of the rated
grid voltage for grid under voltage Level 2
Grid Under Fre-
quency Level 2
0
3.5
Hz
Lower limit for grid under frequency level 2
Grid Over Voltage
Level 1 Trip Time
100
10000
ms
Time for grid over voltage level 1 trip
Table 12: Grid Parameters