Grid parameters – KACO blueplanet 750 - 1000 kVA User Manual

Page 80

Advertising
background image

Page 80

KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0

Parameters

Grid Parameters

Parameters

Min

Max

Unit

Descriptions

Rated Grid Voltage 208

400

V

Rated value of the grid voltage

Rated Grid
Frequency

50

60

Hz

Rated value of the grid frequency

Grid Over Voltage
Level 1

105

130

%

Upper limit expressed as a percentage of the rated
grid voltage for grid overvoltage level 1

Grid Under Voltage
Level 1

75

100

%

Lower limit expressed as a percentage of the rated
grid voltage for grid under voltage Level 1

Grid Over Frequency
Level 1

0

3

Hz

Upper limit for grid over frequency level 1

Grid Under
Frequency Level 1

0

3

Hz

Lower limit for grid under frequency level 1

Frequency Depend-
ant Power Reduc-
tion Mode

0

2

-

Power reduction function dependant on frequency
rise
0: Disable
1: Enable

Power Gradient
Mode

0

5

-

Power gradient function when inverter start
0: Disable
1: Activated when connected to grid after fault
(Germany Medium Voltage Requirements)
2: Activated according to VDE-AR-N 4105
(Germany Low Voltage Requirements)
3: Activated whenever connected to grid
(Italy TERNA Grid Code)

Power Gradient
Ramp

0

600

sec

Ramp time for power gradient

Time Shift

0

6000

sec

Delay time for inverter start

Gate-way Enable

0

1

-

Reserved

Grid Level 2
Protection Enable

0

1

-

Grid level 2 protection function
0: Disable
1: Enable

Grid Over Voltage
Level 2

105

130

%

Upper limit expressed as a percentage of the rated
grid voltage for grid overvoltage level 2

Grid Under Voltage
Level 2

15

100

%

Lower limit expressed as a percentage of the rated
grid voltage for grid under voltage Level 2

Grid Under Fre-
quency Level 2

0

3.5

Hz

Lower limit for grid under frequency level 2

Grid Over Voltage
Level 1 Trip Time

100

10000

ms

Time for grid over voltage level 1 trip

Table 12: Grid Parameters