Time parameters – KACO blueplanet 750 - 1000 kVA User Manual
Page 85

KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0
Page 85
Parameters
Parameters
Min
Max
Unit
Descriptions
RPV Active Period
1
100
Period
Reactive power variation activation period for
Anti-Islanding (RPV)
RPV Period
1
100
Period
Total period of reactive power variation for Anti-
Islanding (RPV) (activate period + deactivate
period)
RPV Q Limit
0
10
%
Limit value of reactive power variation for Anti-
Islanding (RPV)
PJD R-Time
5
30
sec
PWM stop time in case of grid voltage phase delay
fault detection
APS Coeff. 1
1
5
N/A
Proportion constant 1 of reactive power infusion
capability against to the frequency variation for
Anti-Islanding (APS)
APS Coeff. 2
0.01
0.5
N/A
Proportion constant 2 of reactive power infusion
capability against to the frequency variation for
Anti-Islanding (APS)
Band Stop Filter
Ratio
0
9.999
N/A
Proportion constant of band stop filter
Band Stop Filter
Bandwidth
0
999.9
Hz
Bandwidth of Band stop filter
Band Stop Filter
Cut-off Frequency
0
999
Hz
Cut-off frequency of band stop filter
Table 12: Grid Parameters
Time Parameters
Parameters
Min
Max
Unit
Descriptions
Year
2000
3000
-
The present year
Month
1
12
-
The present month
Day
1
31
-
The present date
Time
0
23
-
The present hour
Minute
0
59
-
The present minute
Second
0
59
-
The present second
Table 13: Time Parameters