Digital parameters – KACO blueplanet 750 - 1000 kVA User Manual
Page 86

Page 86
KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0
Parameters
Digital Parameters
Parameters
Min
Max
Unit
Descriptions
DI1 Select
0
20
N/A
DI1 (Digital Input) selection
0: Disable DI1
1: Reserved
2: Reserved
3: Start/Stop operation of the inverter by DI1
(Recognition pattern: 1sec – Stop, 2sec – Start)
4: Start/Stop operation of the inverter by DI1
(Recognition pattern: 200msec – Stop, 400msec
– Start)
5: Stop operation of the inverter by DI1(Inverter
turn off when DI1 signal over {DI1 Check Period}
msec
DO1 Select
0
20
N/A
DO1 (Digital output) selection
0: Fault state is output to DO1
RPC Mode Select
0
2
N/A
The COSPHI control function of the XP-Series
Inverter operates when this parameter is 2.
0: Disable
2: Enable
Power Meter
0
99999999
kWh
PV generation amount check
RS485 Protocol
0
999
-
RS485 communications’ protocol
0: ACI protocol
1: Communication with prolog
2: Communication with PVI-go
RS485 ID
0
999
-
ID for RS485 communication
CAN ID
0
999
-
ID for CAN communication
Argus Box 1
Address
0
99999
-
Argus Box 1 address and type setup
Argus Box 2
Address
0
99999
-
Argus Box 2 address and type setup
Argus Box 3
Address
0
99999
-
Argus Box 3 address and type setup
Argus Box 4
Address
0
99999
-
Argus Box 4 address and type setup
Argus Box 5
Address
0
99999
-
Argus Box 5 address and type setup
Argus Box 6
Address
0
99999
-
Argus Box 6 address and type setup
Argus Box 7
Address
0
99999
-
Argus Box 7 address and type setup
Table 14: Digital Parameters