KACO blueplanet 750 - 1000 kVA User Manual
Page 82

Page 82
KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0
Parameters
Parameters
Min
Max
Unit
Descriptions
Reconnection
Condition Lower
Voltage
-1
100
%
This parameter determines the lower voltage of
“Reconnection condition” range as a percentage
of the rated value.
The negative value represents that the relevant
condition is not checked when an inverter decides
“Reconnection condition”.
Reconnection
Condition Upper
Frequency
-1
3
Hz
This parameter determines the upper frequency of
“Reconnection condition” range as an increment
from the rated value.
The negative value represents that the relevant
condition is not checked when an inverter decides
“Reconnection condition”.
Reconnection
Condition Lower
Frequency
-1
3
Hz
This parameter determines the lower frequency of
“Reconnection condition” range as a decrement
from the rated value.
The negative value represents that the relevant
condition is not checked when an inverter decides
“Reconnection condition”.
Reconnection
Condition Check
Time Normal
0
1800
sec
This parameter is used for time check during
“Reconnection condition” for all the time except
after fault.
Reconnection
Condition Check
Time After Fault
0
1800
sec
This parameter is used for time check during
“Reconnection condition” for after fault only.
Grid Over Frequency
Level 3
0
3
Hz
Upper limit for grid over frequency level 3
Grid Over Frequency
Level 3 Trip Time
40
2000
ms
Time for grid over frequency Level 3 trip
Grid Over Voltage
Level Slow
105
115
%
This parameter represents Upper limit for the
average RMS value of grid voltage as a percentage
of the rated grid voltage.
If the average RMS value of grid voltage exceeds
this parameter setting, fault will be occurred.
VDE-AR-N 4105 (Germany Low Voltage Require-
ments)
Grid Over Voltage
Level Slow Shift
Average Time
-1
3000
sec
This parameter determines how long the average
RMS value of grid voltage will be calculated.
(Low Voltage Requirements: 600 seconds duration)
Negative value means that the relevant function
(Grid Over Voltage level slow) is disabled.
Reconnection
Condition Warning
Delay
0
600
sec
Time delay for Reconnection Condition Warning
Table 12: Grid Parameters