KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0

Parameters

Parameters

Min

Max

Unit

Descriptions

Reconnection
Condition Lower
Voltage

-1

100

%

This parameter determines the lower voltage of
“Reconnection condition” range as a percentage
of the rated value.
The negative value represents that the relevant
condition is not checked when an inverter decides
“Reconnection condition”.

Reconnection
Condition Upper
Frequency

-1

3

Hz

This parameter determines the upper frequency of
“Reconnection condition” range as an increment
from the rated value.
The negative value represents that the relevant
condition is not checked when an inverter decides
“Reconnection condition”.

Reconnection
Condition Lower
Frequency

-1

3

Hz

This parameter determines the lower frequency of
“Reconnection condition” range as a decrement
from the rated value.
The negative value represents that the relevant
condition is not checked when an inverter decides
“Reconnection condition”.

Reconnection
Condition Check
Time Normal

0

1800

sec

This parameter is used for time check during
“Reconnection condition” for all the time except
after fault.

Reconnection
Condition Check
Time After Fault

0

1800

sec

This parameter is used for time check during
“Reconnection condition” for after fault only.

Grid Over Frequency
Level 3

0

3

Hz

Upper limit for grid over frequency level 3

Grid Over Frequency
Level 3 Trip Time

40

2000

ms

Time for grid over frequency Level 3 trip

Grid Over Voltage
Level Slow

105

115

%

This parameter represents Upper limit for the
average RMS value of grid voltage as a percentage
of the rated grid voltage.
If the average RMS value of grid voltage exceeds
this parameter setting, fault will be occurred.
VDE-AR-N 4105 (Germany Low Voltage Require-
ments)

Grid Over Voltage
Level Slow Shift
Average Time

-1

3000

sec

This parameter determines how long the average
RMS value of grid voltage will be calculated.
(Low Voltage Requirements: 600 seconds duration)
Negative value means that the relevant function
(Grid Over Voltage level slow) is disabled.

Reconnection
Condition Warning
Delay

0

600

sec

Time delay for Reconnection Condition Warning

Table 12: Grid Parameters