Q(v) mode – KACO blueplanet 750 - 1000 kVA User Manual

Page 107

Advertising
background image

KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0

Page 107

Parameters

Q(V) Mode

Figure 84: Q(V) Mode using K-Factor

BP SERIES Inverter has a function to control the reactive power according to the grid voltage. When the grid
voltage increases or decreases between rated range, BP SERIES inverter control the reactive power to stabilize
the grid. The grid voltage range where Q(V) function is possible is determined by {Q(V) Control Deadband} and
{Q(V) Control K-Factor}.

Tab

Number Parameter

Min

Max

Default Value

Grid

46

QV Voltage 1

100

110

101

47

QV Voltage 2

90

100

99

48

QV Voltage 3

100

110

106

49

QV Voltage 4

90

100

94

51

QV Inductive Max

0

48

31%

52

QV Capacitive Max

0

48

31%

70

QV Mode Select

0

3

0**

Control

47

COSPHI Control Mode

0

5

2*

60

Q(V) Control Target Voltage

208

440

370

61

Q(V) Control K Factor

0

50

3.1

62

Q(V) Control Deadband

0

100

1%

63

Q(V) Control Ramp Time

0

30000

60sec

Table 27: Related Parameters (ex. BP1000 Model)

**Selection of Q(V) Mode

*Value for Enable of Q(V): 5