Q(v) mode – KACO blueplanet 750 - 1000 kVA User Manual
Page 107

KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0
Page 107
Parameters
Q(V) Mode
Figure 84: Q(V) Mode using K-Factor
BP SERIES Inverter has a function to control the reactive power according to the grid voltage. When the grid
voltage increases or decreases between rated range, BP SERIES inverter control the reactive power to stabilize
the grid. The grid voltage range where Q(V) function is possible is determined by {Q(V) Control Deadband} and
{Q(V) Control K-Factor}.
Tab
Number Parameter
Min
Max
Default Value
Grid
46
QV Voltage 1
100
110
101
47
QV Voltage 2
90
100
99
48
QV Voltage 3
100
110
106
49
QV Voltage 4
90
100
94
51
QV Inductive Max
0
48
31%
52
QV Capacitive Max
0
48
31%
70
QV Mode Select
0
3
0**
Control
47
COSPHI Control Mode
0
5
2*
60
Q(V) Control Target Voltage
208
440
370
61
Q(V) Control K Factor
0
50
3.1
62
Q(V) Control Deadband
0
100
1%
63
Q(V) Control Ramp Time
0
30000
60sec
Table 27: Related Parameters (ex. BP1000 Model)
**Selection of Q(V) Mode
*Value for Enable of Q(V): 5