5 fdpr (frequency dependant power reduction) – KACO blueplanet 750 - 1000 kVA User Manual
Page 109

KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0
Page 109
Parameters
8.2.5 FDPR (Frequency Dependant Power Reduction)
Figure 86: FDPR Function in case of rated frequency 50Hz
BP SERIES Inverter has a function to limit the active power when the grid frequency increases. If grid frequency
variation is higher than {Power Reduction Deactivation Frequency} parameter, the inverter limits the active
power. The limitation level is determined by {Power Reduction Gradient Level}. If the grid frequency exceed
{Grid Over Frequency Level 2}, the inverter will be stopped by ‘Over Frequency Protection’. If the frequency vari-
ation is lower than {Power Reduction Deactivation Frequency} during {Frequency Dependant Power Reduction
Check Time}, the inverter will stop the FDPR.
Tab
Number Parameter
Min
Max
Default Value
Grid
4
Grid Over Frequency Level 1
0
3
0.2
6
Frequency Dependant Power Reduc-
tion Mode
0
2
0
24
Power Reduction Gradient Level
0
100
40%/Hz
25
Power Reduction Deactivation Fre-
quency
0
0.3
0.05Hz
26
Grid Over Frequency Level 2
0
3
1.5
60
Frequency Dependant Power Reduc-
tion Check Time
0
30000
300sec
Table 29: Related Parameters (ex. BP1000 Model)