8.2.5 FDPR (Frequency Dependant Power Reduction)

Figure 86: FDPR Function in case of rated frequency 50Hz

BP SERIES Inverter has a function to limit the active power when the grid frequency increases. If grid frequency
variation is higher than {Power Reduction Deactivation Frequency} parameter, the inverter limits the active
power. The limitation level is determined by {Power Reduction Gradient Level}. If the grid frequency exceed
{Grid Over Frequency Level 2}, the inverter will be stopped by ‘Over Frequency Protection’. If the frequency vari-
ation is lower than {Power Reduction Deactivation Frequency} during {Frequency Dependant Power Reduction
Check Time}, the inverter will stop the FDPR.

Tab

Number Parameter

Min

Max

Default Value

Grid

4

Grid Over Frequency Level 1

0

3

0.2

6

Frequency Dependant Power Reduc-
tion Mode

0

2

0

24

Power Reduction Gradient Level

0

100

40%/Hz

25

Power Reduction Deactivation Fre-
quency

0

0.3

0.05Hz

26

Grid Over Frequency Level 2

0

3

1.5

60

Frequency Dependant Power Reduc-
tion Check Time

0

30000

300sec

Table 29: Related Parameters (ex. BP1000 Model)