Fixed q mode – KACO blueplanet 750 - 1000 kVA User Manual
Page 104

Page 104
KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0
Parameters
Fixed Q Mode
Figure 82: One of the Example about Fixed Q
BP SERIES Inverter has a function to control the reactive power. Above the figure, the red-line is apparent
power, blue-line is active power, purple-line is reactive power, and the green-dot line is power factor. If {COSPHI
Reactive Power Internal} parameter is set to 15%, Inverter can control the reactive power as the above figure.
If apparent power exceed 1MVA by changing reactive power, active power decreases to maintain apparent
power. Fixed Q mode is active when {COSPHI Control Mode} value is set to 3.
Tab
Number Parameter
Min
Max
Default Value
Grid
74
Reactive Power Ramp
1
30000
10sec
Controller
47
COSPHI Control Mode
0
5
2*
49
COSPHI Reactive Power Internal
-99.9
99.9
0
Table 25: Related Parameters (ex. BP1000 Model)
*Value for Enable of Fixed Q: 3