Parameters
Parameters
Min
Max
Unit
Descriptions
PV Voltage Check
Time
0
3600
sec
Inverter operation mode is changed if PV output
voltage is higher than the setting value of {MPPT V
Start} during time delay of {PV Voltage Check
Time} (When {RPO Enable} is ‘1: Enable’)
RPO Enable
0
1
-
0: RPO Mode Disable
1: RPO Mode Enable
Table 10: PV Array Parameters
Inverter Parameters
Parameters
Min
Max
Unit
Descriptions
Transformer & Type 0
1054
N/A
This parameter determines device specific informa-
tion such as a switch type on DC side and whether
the inverter has an internal transformer
Inverter Capacity
100
1000
kW
Power Capacity of the inverter
Inverter OverCurrent
Level
0
200
%
Upper limit for inverter over current fault
Current Limit
0
150
%
Limit of current which produces from the inverter
Cabinet Tempera-
ture Maximum
30
70
°C
Upper limit for cabinet over temperature warning
Cabinet Tempera-
ture Minimum
-25
10
°C
Lower limit for cabinet under temperature warning
PEBB Temperature
Unbalance Level
5
30
°C
Limit of Temperature gap between PEBBs
Test Protection
Function Mode
0
1
N/A
Grid voltage and frequency protection level test
mode using AC Simulator
(Only Transformer-Less model)
PEBB Temperature
Warning Level
50
150
°C
Upper limit of the maximum temperature of PEBB
(warning level)
Inverter Sub
Capacity
70
999
kW
Inverter capacity to support the diversification of
model
PEBB Current
Unbalance Limit
0
100
%
Limit of current gap between PEBBs
Table 11: Inverter Parameters