KACO blueplanet 750 - 1000 kVA User Manual

Page 90

Advertising
background image

Page 90

KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0

Parameters

Parameters

Min

Max

Unit

Parameters

Asynchronous Fault
Enable

0

1

-

Reserved

Grid Positive
Sequence

0

999.9

V

Positive sequence value of grid

COSPHI Control
Mode

0

5

-

Reactive power supply method in Internal mode
and RPC mode
0: disabled
1: fixed P
2: fixed cosφ
3: fixed Q
4: Cosφ (P/Pn)
5: Q(U)

COSPHI Power
Factor Internal

-1

1

-

Power factor reference in internal mode

COSPHI Reactive
Power Internal

-99.9

99.9

%

Reactive power reference in internal mode
(Percent for rated one)

COSPHI Power
Factor Actual

-1

1

-

The actual power factor value that is applied
(Read only)

COSPHI Power
Factor RPC

-1

1

-

Power factor reference in RPC mode

COSPHI Reactive
Power RPC

-99.9

99.9

%

Reactive power reference in RPC mode
(percent for rated one)

COSPHI Stray Ratio 0

2

The setup value for COSPHI control

Positive Sequence
PLL Enable

0

1

-

The use of grid voltage of positive sequence at PLL

FRT K Factor

0

10

-

The setup constant during FRT control

FRT IQ Ramp

0

30000

msec

The slope of active power supply during FRT
control

FRT IQ Ramp Time

0

30000

msec

The time that use a slope changed by FRT IQ ramp
parameter

Positive Sequence
LPF

0

999.9

Hz

The cutoff frequency for RMS value of positive
sequence

PLL Freq LPF

0

999.9

Hz

The cutoff frequency for frequency value detec-
tion of PLL

Q(V) Control Target
Voltage

208

440

V

Value of Q(V) Control Target Voltage

Q(V) Control K
Factor

0

50

-

A setup constant for voltage control of BDEW

Q(V) Control
Deadband

0

100

%

Non-applicable voltage range during voltage
control of BDEW

Table 16: Controller Parameters