KACO blueplanet 750 - 1000 kVA User Manual
Page 90

Page 90
KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0
Parameters
Parameters
Min
Max
Unit
Parameters
Asynchronous Fault
Enable
0
1
-
Reserved
Grid Positive
Sequence
0
999.9
V
Positive sequence value of grid
COSPHI Control
Mode
0
5
-
Reactive power supply method in Internal mode
and RPC mode
0: disabled
1: fixed P
2: fixed cosφ
3: fixed Q
4: Cosφ (P/Pn)
5: Q(U)
COSPHI Power
Factor Internal
-1
1
-
Power factor reference in internal mode
COSPHI Reactive
Power Internal
-99.9
99.9
%
Reactive power reference in internal mode
(Percent for rated one)
COSPHI Power
Factor Actual
-1
1
-
The actual power factor value that is applied
(Read only)
COSPHI Power
Factor RPC
-1
1
-
Power factor reference in RPC mode
COSPHI Reactive
Power RPC
-99.9
99.9
%
Reactive power reference in RPC mode
(percent for rated one)
COSPHI Stray Ratio 0
2
The setup value for COSPHI control
Positive Sequence
PLL Enable
0
1
-
The use of grid voltage of positive sequence at PLL
FRT K Factor
0
10
-
The setup constant during FRT control
FRT IQ Ramp
0
30000
msec
The slope of active power supply during FRT
control
FRT IQ Ramp Time
0
30000
msec
The time that use a slope changed by FRT IQ ramp
parameter
Positive Sequence
LPF
0
999.9
Hz
The cutoff frequency for RMS value of positive
sequence
PLL Freq LPF
0
999.9
Hz
The cutoff frequency for frequency value detec-
tion of PLL
Q(V) Control Target
Voltage
208
440
V
Value of Q(V) Control Target Voltage
Q(V) Control K
Factor
0
50
-
A setup constant for voltage control of BDEW
Q(V) Control
Deadband
0
100
%
Non-applicable voltage range during voltage
control of BDEW
Table 16: Controller Parameters