2 functions, 1 mppt (maximum power point tracking) function – KACO blueplanet 750 - 1000 kVA User Manual

Page 96

Advertising
background image

Page 96

KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0

Parameters

8.2 Functions

8.2.1 MPPT (Maximum Power Point Tracking) Function

Figure 73: Characteristic of PV Curve

BP SERIES Inverter start operation when Voc (open circuit voltage) is higher than {MPPT V Start} during {MPPT
T Start} and initial MPP Voltage is start at {MPP Factor} * Voc, and MPP voltage is changed within the MPP range
to generate maximum power. Default value of MPPT Parameters can be changed by Model.

Tab

Number Parameter

Min

Max

Default Value

PV Array

0

MPPT Eanble

0

1

1

1

MPPT V Maximum

0

830

830V

2

MPPT V Start

200

800

700Vc

3

MPPT T Start

0

3600

900sec

6

MPPT V Minimum

200

800

505V

7

DC Over Voltage Level

300

1020

1020V

9

MPP Factor

0

1

0.8

12

PV Operation Level

900

1020

1000V

Table 20: Related Parameters (ex. BP1000 Model)

Advertising