2 operating dc voltage range – KACO blueplanet 750 - 1000 kVA User Manual

Page 97

Advertising
background image

KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0

Page 97

Parameters

8.2.2 Operating DC voltage range

Figure 74: Inverter Operating PV Voltage Range

The range of possible operational input voltage is from {MPPT V Minimum} to {PV Operation Level}. The picture
above shows that the output power decreases linearly where the input power is from {MPPT V Maximum} to
{PV Operation Level}.

Tab

Number Parameter

Min

Max

Default Value

PV Array

1

MPPT V Maximum

0

830

830V

6

MPPT V Minimum

200

800

505V

12

PV Operation Level

900

1020

1000V

13

PV Over DC V Mode

0

1

1

Table 21: Related Parameters (ex. BP1000 Model)