KACO blueplanet 750 - 1000 kVA User Manual

Page 117

Advertising
background image

KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0

Page 117

Parameters

• Grid Under Voltage Levels

» Grid Under Voltage Level 1 - Transfer to FRT mode.

» Grid Under Voltage Level 2 - Inverter stops its operation with ‘Grid Under Voltage Level 2 Fault’ when the
grid voltage below ‘Grid Under Voltage Level 2’ sustains over “Grid Under Voltage Trip Time 2”.

» Grid Under Voltage Trip Time 1 - Permissible grid voltage under ‘Grid under Voltage Level 1’ time.

» Grid Under Voltage Trip Time 2 - Permissible grid voltage under ‘Grid Under Voltage Level 2’ time.

Figure 95: FRT Parameters

Advertising