KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0

Storage/Installation/Start-up

Figure 20: AC connection

5.5.3 Requirements for cable routing between transformer and inverter
(AC connection)

WARNING

Fire hazard due to overheating of cables
Differing cable lengths result in overheating of the cables.

All line conductors from the inverter to the transformer must be of the same length.

The followings are requirements for avoiding current imbalances and cable overheating;

The minimum size of conductor must be designed based on UL1741, NEC standard and table24 of IEC62109-1
2010.

The AC cables must be bundled in a three-phase system.(Required to use cables of the equal type, diameter
and length)

Between the transformer and the inverter there must be four separate cable routes for the AC cables.

Lay one A, B and C line conductor in each cable route. Ensure that the distance between the cable bundles
at least doubles the cable diameter.

Figure 21: Arrangement of AC cables with 4-cable-per-line conductor (example)