Parameters

Cosphi (P/Pn) Mode

Figure 83: One of the Example about Cosphi (P/Pn) Mode

BP SERIES Inverter has a function to control the power factor according to the active power to grid. The maxi-
mum setup point of both PF and active power is 10 points and the maximum required value of PF for Cosphi
(P/Pn) is 0.9.

Tab

Number Parameter

Min

Max

Default Value

Control

47

COSPHI Control Mode

0

5

2*

65

COS (P/Pn) Ramp Time

0

30000

10

66

COSPHI_1

-1

1

1

67

P2

0

100

0%

68

COSPHI_1

-1

1

1

69

P2

0

100

0%

70

COSPHI_3

-1

1

1

71

P3

0

100

0%

72

COSPHI_4

-1

1

1

73

P4

0

100

0%

74

COSPHI_5

-1

1

1

75

P5

0

100

0%

76

COSPHI_6

-1

1

1

77

P6

0

100

0%

78

COSPHI_7

-1

1

1

Table 26: Related Parameters (ex. BP1000 Model)