Parameters
Parameters
Min
Max
Unit
Parameters
Cabinet FAN PWM 0
100
-
Reserved
Remote Power
Control Ramp
0
600
sec
The slope of inverter output active poser when
remote power is controlled
Total Yield
0
30000
kWh
Check total yield of generation (Read only)
Today Yield
0
30000
kWh
Check day yield of generation (Read only)
IIVCD P Gain
0
299.99
-
d-axis P gain of inverter output voltage controller
for initial voltage build-up
IIVCD I Gain
0
299.99
-
d-axis I gain of inverter output voltage controller
for initial voltage build-up
IIVCQ P Gain
0
299.99
-
q-axis P gain of inverter output voltage controller
for initial voltage build-up
IIVCQ I Gain
0
299.99
-
q-axis I gain of inverter output voltage controller
for initial voltage build-up
AAI(Active Anti-
Islanding) Mode
0
3
-
Anti-Islanding control mode selection
0: disable
1: APS enable
2: RPV enable
3: APS + RPV enable
APS Upper DB
0.02
3
Hz
Upper limit of frequency for APS
Reactive Power
Limit
0
299.99
-
Reactive power limits of reactive power infusion
capability against to the frequency variation for
Anti-Islanding (APS)
Wind Speed
0
299.9
-
Reserved
Power Derating
Enable
0
1
-
The use of power decline controller according to
PEBB temperature, Yes(1) NO(0)
Power Derating
Enable Temperature
50
100
-
Temperature level which starts decreasing power
according to PEBB temperature
Power Derating
Disable Temperature
40
90
-
Temperature level which stops decreasing power
according to PEBB temperature
Power Derating
Reference Tempera-
ture
45
95
-
PEBB temperature reference value
Power Derating P
Gain
0
10
-
Power declining controller’s P gain according to
PEBB temperature
Grid IIR Filter Cutoff
Frequency
0
10
Hz
Filter cutoff frequency used for RMS value detec-
tion of grid voltage
Asynchronous Fault
Count
0
100
-
Reserved
Table 16: Controller Parameters