KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0
Faults and Warnings
Message
Code
Description
CAN TX Failure
135
CAN bus communication transmission failure
CAN RX Failure
136
CAN bus communication reception failure
CAN EP Failure
137
CAN bus communication Error-Passive error
CAN Bus-Off
138
CAN bus communication Bus-off error
CAN Wrong Message
139
Reception of Wrong message in CAN bus communication
CAN Time Out
140
Time out in CAN bus communication
CAN Multiple Master
141
There are multiple Masters in CAN bus communication
Table 5: Warning
6.2 Fault
Message
Code
Description
PV Over Voltage
1
PV voltage exceeds the parameter [DC over voltage Level]
PV Over Current
2
PV current exceeds the parameter [DC over current Level]
CB10 (PV CB) Trip
4
PV side circuit breaker (DS10) tripped
PV Polarity Failure
5
Polarity (+, -) of PV side is reversed
Ground Fault
6
PV side ground fault
Inv. Over Current (PEBB 1)
7
Inverter Output Current over one-third of the parameter [Inverter Over
Current Level]
Inv. Over Current (PEBB 2)
8
Inverter Output Current over one-third of the parameter [Inverter Over
Current Level]
Inv. Over Current (PEBB 3) 9
Inverter Output Current over one-third of the parameter [Inverter Over
Current Level]
MC21 (Inv. MC of PEBB 1)
Failure
15
Inverter side contactor (MC21 of PEBB 1) failure
Inv. Phase Order
16
Phase order failure on the inverter side, wrong phase rotation
Inductor or TR Over Temp. 18
Inductor or Transformer temperature over 150°C
Inv. Current Unbalance
19
The unbalanced current of inverter side
PEBB(1) IGBT Fault
20
PEBB 1 IGBT failure
PEBB(2) IGBT Fault
21
PEBB 2 IGBT failure
PEBB(3) IGBT Fault
22
PEBB 3 IGBT failure
PEBB Over Temp. Analog
24
The temperature of the heat-sink over the parameter [Heatsink OT
Level] (Analog)
PEBB Over Temp. Digital
25
The temperature of the heat-sink over 100°C (Digital)
Table 6: Fault