3 solution for error code, 1 warning – KACO blueplanet 750 - 1000 kVA User Manual

Page 62

Advertising
background image

Page 62

KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0

Faults and Warnings

6.3 Solution for Error code

The Inverter can detect faults during operation. The inverter will display the fault in the CMT. Faults are indi-
cated in the CMT with an error code, and a plain text message with the error code and system plant name in
the text line will be sent to the system operator (only available if purchased and configured during setup). This
section describes how to recognize the types of faults and how to correct these faults.

6.3.1 Warning

Code Message

Warning description

Possible problem and Solution(s)

81

SP1 (PV SP) Failure

Failure of the PV side surge
protector (SP1)

Possible problem
• Lightning strike on or near the PV system
wiring
Solution(s)
• Visual inspection
• Change the SPD

100

PEBB Over Temp.
Warning

The temperature of the PEBB
(Power Electronics Building
Block) over 85°C (185°F)

Possible problem
• PEBB Fan Failure
Solution(s)
• Clean the filters or PEBB heat-sink fins
• Change the PEBB Fan

101

PEBB Fan Failure

Failure of a PEBB (Power Elec-
tronics Building Block) fan

Possible problem
• PEBB Fan Failure
Solution(s)
• Change the PEBB Fan

120

Test Mode

The system is working in test
mode

Possible problem
• The system is working in test mode
Solution(s)
• Change the parameters in the GUI

130

Cabinet Over Temp.
Warning

The temperature of the cabinet
over the parameter [Cabinet
Temperature Maximum]

Possible problem
• Cabinet Fan Failure
Solution(s)
• Clean the air filters
• Change the cabinet fan

131

Cabinet Under Temp.
Warning

The temperature of the cabinet
falls below operational param-
eters
[Cabinet Temperature Minimum]

Possible problem
• Ambient temperature is too low for
operation

134

SMPS Warning

Failure of the control SMPS

Possible problem
• Failure of the control SMPS
Solution(s)
• Change the control SMPS

Table 7: Warning