KACO blueplanet 750 - 1000 kVA User Manual
Page 84

Page 84
KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0
Parameters
Parameters
Min
Max
Unit
Descriptions
Frequency Depend-
ant Power Reduc-
tion Check Time
0
30000
sec
Frequency holding time for deactivation of power
limitation against to grid frequency increase
(CEI 0-16 grid code only)
Voltage Dependant
Power Reduction
Mode
0
2
N/A
Limitation of power according to grid voltage
increase
1: Step reduction
2: Linear reduction
Voltage Dependant
Power Reduction
Voltage Level1
0
999
%
Voltage level 1 for power limitation function
against to grid voltage increase
Voltage Dependant
Power Reduction
Voltage Level2
0
999
%
Voltage level 2 for power limitation function
against to grid voltage increase
Voltage Dependant
Power Reduction
Ramp
0
30000
sec
Power reduction response time at power limitation
function activation against to grid voltage increase
Voltage Dependant
Power Reduction
Level
0
100
%
Amount of power limitation at power limitation
function activation against to grid voltage increase
Variable Rated
Current Enable
0
1
N/A
Rated current level increase function when grid
voltage decrease
Variable Rated
Current Check Time
0
999
sec
Rated current level increase function holding time
when grid voltage decrease
Variable Rated
Current Ramp
0
999
sec
Rated current level recovery response time at
“Variable Rated Current” function deactivation
Moving Average
RMS Time Window
0
60
sec
Time window for moving average RMS calculation
of grid voltage
QV Mode Select
0
3
N/A
Q(V) mode selection
Grid Over Voltage
Level1 Trip Time
Scale
1
9999
N/A
Time scale for grid over voltage Level 3 trip
Active Damping
Limit
0
999
N/A
Limit value of active current value change amount
when using active damping function
Power Factor Limit
0.01
1
N/A
Limit value can be set using Fixed COSθ control
Reactive Power
Ramp
1
9999
sec
Slop of inverter output reactive power
(Apply when using Fixed Q, Fixed COSθ control)
RPV Q
-99.9
99.9
%
Reactive power variation value for Anti-Islanding
(RPV)
RPV Time
0.001
9.999
Period
Reactive power variation period for Anti-Islanding
(RPV) (Based on one cycle)
Table 12: Grid Parameters